Chapter 8: Troubleshooting
309
The components list expands and shows the power supply fans, which
server as the Cooling Unit of the VTrak Ex30 enclosure.
Note that the fans for power supply 2 (PSU 2) have failed.
3. Click the Back View icon on the Device tab.
4. Mouse-over the picture of the enclosure.
A popup messages displays the status of each component.
When a power supply fan fails, you must replace the power supply. See
“Replacing a Power Supply” on page 250 for more information.
If the system reports a fan malfunction, contact Technical Support (see
page 351) immediately to schedule replacement of the suspect power supply
as soon as possible. Running the unit in this condition for more than three
weeks may shorten subsystem life and void your warranty.
Click the View button
Note the red X icon
Note the red X icons